How do I set Occupied / Unoccupied schedules for N2 devices with the S4 Open appliance?

Author:
Steve Jones
Date added:
Monday, 12 July 2010
favoured:
1 Favour

Answer

Most N2 devices do not contain a time of day clock that you can access directly. They do have an on-board clock that can be synchronized with the head end and is used as a fallback when the N2 device becomes disconncted from the head end. In normal operation they completely rely on a supervisory controller to tell them if they should be in Occupied or UnOccupied mode by toggling a binary point.

Typically, you’ll see set points for Occupied mode and another pair for UnOccupied mode. Simply have your new HMI or another (BACnet or OPC as appropriate) controller toggle the Occupied point in each N2 device to indicate the mode that you want each controller to operate in.

Check the manufacturer documentation for each N2 device and application supported by it for the correct point to toggle the Occupied / UnOccupied status of the device and the point names assigned for the setpoints.

Category

Tags for this item

Comments  

 
#1 Steve Jones 2011-02-12 14:05
Depending on how your N2 device is programmed you might be required to send the Occupied / Unoccupied command as an N2 Override instead of as a N2 Write.
Quote
 

Add comment


Security code
Refresh

Search the Site

Distributor/Integrator Locator

Stay Informed

Subscribe to Our Newsletter

Email Address:

First Name:

Last Name:

We'd Like Your Opinion

busyLoading Poll...
You are here  : Home Support and Downloads FAQs S4 Open Appliances - General Information How do I set Occupied / Unoccupied schedules for N2 devices with the S4 Open appliance?
Windows Embedded Partner Logo
follow us on twitter
follow us on linkedin